Airstream Density Calculator

Airstream Density Calculator

Determines airstream density at the fan inlet from inlet temperature, atmospheric pressure, fan inlet static pressure and airstream moisture.

Atmospheric pressure basis

Barometric pressure is typically used for on-site testing. Site elevation is used in all other instances.

Airstream moisture basis

Choose the moisture value you have for the airstream.

Fan inlet conditions
°F
%
ft-asl
in. wg

Use a minus sign for below atmospheric.

Results

Actual density of mixture
0.0750
lbm/ft³
Density factors, ACGIH method
Density factor, elevation (dfe) 1.000
Density factor, pressure (dfp) 1.000
Density factor, temperature (dft) 1.000
Density factor, moisture (dfm) 1.000
Density factor (df) 1.000
Airstream properties
Humid volume 13.33 ft³ mix/lbm dry air
Moist air enthalpy 16.8 Btu/lbm dry air
Calculator notes and assumptions

Application

This calculator is for dry air having an isentropic exponent of 1.4 with the addition of various amounts of water (moisture) in vapor phase. It is not applicable to other gases or condensibles.

Fan inlet temperature units and entry

All temperatures are airstream temperatures at the fan inlet and in degrees Fahrenheit (°F). Enter temperatures as actual (gauge) values and not in absolute values.

Absolute temperature used for calculations is 530 °R.

Dry bulb temperature is the temperature measured directly by a thermometer or other direct temperature sensing device.

Wet bulb temperature is the temperature at which water (as a liquid) brings the air to saturation adiabatically and at the same temperature. It can be measured by wrapping a wettable material (fabric) around the bulb of a dry bulb thermometer and moving the airstream across the wetted material at 1,000 fpm or higher. The wet bulb temperature is the temperature at which the thermometer temperature reading first stabilizes.

Atmospheric pressure units and entry

When working on the basis of site elevation, enter as feet above sea level (ft-asl). If unknown, common practice is to use the elevation listed by either the closest local airport or National Weather Service Forecast site.

When working on the basis of barometric pressure, enter the site actual barometric pressure in inches of mercury (in. Hg). If a local barometric pressure gauge is not available or useable, common practice is to use the barometric pressure listed at the closest local airport or National Weather Service Forecast site.

Fan inlet (duct) pressure units and entry

All pressures are in inches of water gauge (in. wg, or Pg) and as measured at the fan inlet.

Enter pressures as actual gauge pressure values using + (positive) or − (negative) to indicate above or below standard atmospheric pressure. Do not enter absolute values.

Absolute pressure used for calculations is 407 inches water gauge.

Airstream moisture

Enter the water vapor moisture content as either Relative Humidity (ø) or Specific Humidity (ω).

When using Relative Humidity (ø), enter as a percentage (%). Relative Humidity is the ratio of the actual partial pressure of the water vapor in air to its saturation pressure at a corresponding dry bulb temperature. If the airstream enters the system from ambient conditions and no work is done on the airstream to change its Relative Humidity (change in temperature, pressure, etc.), then acceptable practice is to use the Relative Humidity listed at the closest local airport or National Weather Service Forecast site.

When using Specific Humidity (ω), enter as pounds of water vapor per pound of dry air (lbm-water vapor/lbm-dry air). Specific Humidity may sometimes be listed in units of grains-water vapor instead of lbm-water vapor, in which case it should be converted to lbm-water vapor. The common unit conversion is 7,000 grains = 1 lbm.

Specific Humidity is sometimes referenced as the airstream Humidity Ratio, Moisture Content, or Mixing Ratio.

Source and calculation bases are from work done by James N. Friedman, PE, CIH using ACGIH® and ASHRAE standards, formulas, guidelines and recommended practices for dry and moist air when modeled as an Ideal Gas. These calculations are intended as guidelines for use. User assumes all risks and liabilities.